Wire colors & phases

The US electrical color code at a glance — how to tell hot from neutral from ground, and how the phases are marked in single- and three-phase systems.

Back to AstralLearn

Single-phase 120/240V

Most homes

  • Hot — L1 — Black
  • Hot — L2 — Redthe second hot in 240V circuits
  • Neutral — White
  • Ground — Green/baregreen, green-yellow, or bare copper

Three-phase 208Y/120V

Light commercial

  • Phase A — Black
  • Phase B — Red
  • Phase C — Blue
  • Neutral — White
  • Ground — Green/bare

Three-phase 480Y/277V

Commercial / industrial

  • Phase A — Brown
  • Phase B — Orange
  • Phase C — Yellow
  • Neutral — Gray
  • Ground — Green/bare
What the NEC actually requires: only two colors are mandated — the grounded (neutral) conductor must be white or gray, and the equipment ground must be green, green-with-yellow, or bare. The hot colors above are the common convention, not a blanket NEC rule; what matters is that hots are clearly distinguishable and consistent throughout the building.
The high-leg rule: on a 120/240V high-leg (delta) system, the phase with the higher voltage to ground (~208V) must be marked orange — NEC 110.15. That's why orange is avoided for a normal phase where a high leg could exist.
Identifying a circuit: check voltage (120 vs 240 vs 208 vs 480), how many hots (one = 120V, two = 240V single-phase, three = three-phase), whether there's a neutral, and always the ground. A labeled panel directory makes it obvious — and is required by code.

Educational reference — verify against the current NEC and your AHJ. Work that has to pass inspection? Call a licensed C-10 → (650) 562-8594.